Nominal input voltage range | 100 V AC ... 240 V AC |
---|---|
Input voltage range | 85 V AC ... 264 V AC |
90 V DC ... 250 V DC | |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Current consumption | approx. 2.4 A (120 V AC) |
1.3 A (230 V AC) | |
Nominal power consumption | 264 W |
Inrush current | < 15 A (typical) |
Mains buffering time | > 40 ms (120 V AC) |
> 40 ms (230 V AC) | |
Input fuse | 6.3 A (slow-blow, internal) |
Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 22.5 V DC ... 28.5 V DC |
Nominal output current (IN) | 10 A (up to 60°C) |
POWER BOOST (IBoost) | 15 A |
Derating | 60 °C ... 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Residual ripple | < 100 mVPP |
Output power | 240 W |
Typical response time | < 1 s |
Maximum power dissipation in no-load condition | 4 W |
Power loss nominal load max. | 33 W |
General
Net weight | 1.3 kg |
---|---|
Operating voltage display | Green LED |
Efficiency | > 88 % |
Insulation voltage input/output | 4 kV AC (routine test) |
2 kV AC (type test) | |
Protection class | I |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Mounting position | horizontal DIN rail NS 35, EN 60715 |