TRIO-PS-IP67/3AC/24DC/20 – 1039829 Trio 3pha, 20A IP 67
Thông tin kỹ thuật:
Your advantages
- Direct installation at the load in the field reduces cable lengths and saves space in the control cabinet
- The robust design (die-cast aluminum housing) ensures high system availability, thanks to resistance to extreme environmental conditions (temperature, dust, and water)
- Reliable startup of high loads, thanks to the dynamic boost
- High efficiency of > 93%, thanks to low power losses
Ambient conditions
Degree of protection | IP67 |
---|---|
Ambient temperature (operation) | -25 °C ... 85 °C (Derating > 60 °C (3 AC): 2,5 %/K / > 50 °C (2 AC): 2,5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 4 |
Installation height | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
Nominal input voltage range | 3x 400 V AC ... 500 V AC |
---|---|
2x 400 V AC ... 500 V AC | |
Input voltage range | 3x 400 V AC ... 500 V AC -20 % ....+15 % |
2x 400 V AC ... 500 V AC -10 % ... +15 % | |
AC frequency range | 50 Hz ... 60 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 3x 1.2 A (400 V AC) |
3x 1 A (500 V AC) | |
2x 2.3 A (400 V AC) | |
2x 1.9 A (500 V AC) | |
Nominal power consumption | 39 W |
Inrush current | typ. 22 A (at 25 °C) |
Mains buffering time | typ. 10 ms (400 V AC) |
typ. 20 ms (500 V AC) | |
Input fuse | 3.15 A (internal (device protection), slow-blow) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Nominal output current (IN) | 20 A |
Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
Derating | > 60 °C ... 70 °C (2.5%/K) |
Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | ≤ 20 mVPP |
Output power | 480 W |
Typical response time | < 1 s |
Maximum power dissipation in no-load condition | < 2 W (400 V AC) |
< 2.5 W (480 V AC) | |
Power loss nominal load max. | < 44 W (400 V AC) |
< 44 W (480 V AC) |