ELR W3- 24DC/500AC- 9I – 2297057- 4 in1 Motor starter
Thông tin kỹ thuật:
Input data
Input name | Control input right/left |
---|---|
Rated actuating voltage UC | 24 V DC |
Triggering voltage range | 19.2 V DC ... 30 V DC |
Rated actuating current IC | 5 mA |
Switching threshold | 9.6 V (“0” signal) |
19.2 V (“1” signal) | |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Typical response time | < 35 ms |
Typical turn-off time | < 40 ms |
Output data load output
Output name | AC output |
---|---|
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC ... 550 V AC |
Rated operating current Ie | 9 A (AC-51) |
6.5 A (AC-53a) | |
Mains frequency | 50/60 Hz |
Load current range | 1.5 A ... 9 A (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Residual voltage | < 0.5 V |
Surge current | 100 A (t = 10 ms) |
Type of protection | Surge protection |
Output data reply output
Output name | Acknowledge output |
---|---|
Note | Confirmation: floating change-over contact, signal contact |
Contact type | 1 PDT |
Switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
2 A (24 V, DC13) |
General
Motor starter type | Reversing starter |
---|---|
Switching frequency | ≤ 2 Hz (Load-dependent) |
Mounting position | Vertical (horizontal DIN rail) |
Mounting type | DIN rail mounting |
Assembly instructions | Can be aligned with spacing = 20 mm |
Operating mode | 100% operating factor |
Maximum power dissipation | 14.6 W |
Minimum power dissipation | 1.1 W |
Operating voltage display | Green LED |
Status display | Yellow LED |
Indication | Red LED |