MACX MCR-EX-SL-RPSSI-I – 2865340 Cách ly phòng nổ


Mã sản phẩm: MACX MCR-EX-SL-RPSSI-I - 2865340

Nhà sản xuất: PHOENIX CONTACT

Mô tả:

MACX MCR-EX-SL-RPSSI-I - 2865340  bộ cách ly phòng nổ Ex i. MACX MCR-EX-SL-RPSSI-I - 2865340 dùng cho sensor có 2 dây cấp nguồn từ PLC hoặc DCS qua bộ chuyển đổi . MACX MCR-EX-SL-RPSSI-I - 2865340  tương tích với chuẩn Hart. MACX MCR-EX-SL-RPSSI-I - 2865340 cách ly chiều đạt chứng chỉ  SIL 2 theo IEC 61508.

Giá bán lẻ: Vui lòng liên hệ

Thông tin kỹ thuật:

Your advantages

  • 0/4 mA ... 20 mA input, intrinsically safe, [Ex ia], powered and not powered
  • Measuring transducer supply voltage > 16 V
  • 0/4 mA ... 20 mA output, active up to 1000  load or passive
  • Bidirectional HART signal transmission
  • Error indication according to NAMUR NE 43
  • SIL 2 according to IEC 61508/EN 61508
  • Installation in zone 2, protection type "ec" (EN 60079-7) permitted
  • 3-way electrical isolation
  • Power supply possible via DIN rail connector
  • Plug-in connection terminal blocks, screw connection technology, with integrated sockets for HART communicators
  • Housing width: 12.5 mm
  • Minimal power dissipation
  • High transmission accuracy

Input data

Signal input Active current input, intrinsically safe
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Polarization and surge protection Yes
Signal input Passive current input, intrinsically safe
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Back to top
 

Output data

Signal output Current output (active and passive)
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Signal output Current output (active and passive)
Current output signal 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)