Thông tin kỹ thuật:
General
EN type | T3 |
---|---|
IEC power supply system | TT |
TN-S | |
Number of ports | One |
Mode of protection | L-N |
L-PE | |
N-PE | |
(L+) - (L-) | |
(L+/L-) - PE | |
Mounting type | DIN rail: 35 mm |
Color | light grey RAL 7035 |
traffic grey A RAL 7042 | |
Housing material | PA 6.6-FR 20 % GF |
PA 6.6-FR | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 2 |
Surge protection fault message | Optical, remote indicator contact |
Protective circuit
Nominal voltage UN | 230 V AC (TN-S) |
---|---|
230 V AC (TT - only in use with RCD) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 264 V AC |
230 V DC | |
Rated load current IL | 26 A (30 °C) |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In (8/20) µs | 3 kA |
Standby power consumption PC | ≤ 275 mVA (at UREF) |
≤ 300 mVA (at UC) | |
Reference test voltage UREF | 255 V AC |
Combination wave UOC | 6 kV |
Voltage protection level Up (L-N) | ≤ 1.35 kV |
Voltage protection level Up (L-PE) | ≤ 1.5 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
TOV behavior at UT (L-N) | 440 V AC (5 s / withstand mode) |
440 V AC (120 min / withstand mode) | |
TOV behavior at UT (L-PE) | 440 V AC (5 s / withstand mode) |
440 V AC (120 min / withstand mode) | |
1455 V AC (200 ms / safe failure mode) | |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / safe failure mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Short-circuit current rating ISCCR | 1.5 kA AC |
0.25 kA DC | |
Max. backup fuse with branch wiring | not required |
Maximum backup fuse for through wiring | 25 A (gG / B / C) |