VAL-MB-T2 1500DC-PV/2+V-FM – 2905646 Chống sét


Mã sản phẩm: VAL-MB-T2 1500DC-PV/2+V-FM-2905646

Nhà sản xuất: PHOENIX CONTACT

Mô tả:

VAL-MB-T2 1500DC-PV/2+V-FM-2905646 dòng chống sét type 2 chuyên dụng cho Solar với điện áp tối đa tới 1500VDC.VAL-MB-T2 1500DC-PV/2+V-FM-2905646 có dòng cắt tối đa Imax = 40kA(8/20us) và dòng chạy chạy qua liên tục 50A.

Giá bán lẻ: Vui lòng liên hệ

Thông tin kỹ thuật:

Sản phẩm liên quan ( related products)

Mã hàng Mã sản phẩm Lưu ý
1033725 VAL-MS 1500DC-PV/2+V-FM
1033708 VAL-MS 1500DC-PV/2+V
2800628 VAL-MS 1000DC-PV/2+V
2905646 VAL-MB-T2 1500DC-PV/2+V-FM
2800627 VAL-MS 1000DC-PV/2+V-FM
2905640 VAL-MB-T1/T2 1500DC-PV/2+V-FM Chống sét Type 1& Type 2
2905641 VAL-MB-T1/T2 1500DC-PV/2+V Chống sét Type 1& Type 2

Sơ đồ đấu nối ( Wiring diagram)

Catalog & user manual VAL-MB-T2 1500DC-PV/2+V-FM

Down load catalog theo link

Thông số kỹ thuật chi tiết

IEC test classification PV II
PV T2
EN type T2
SPD failure behavior OCM (Open-circuit mode)
Connection configuration Y configuration
Installation location Interior zone
Accessibility Accessible
Installation location of the disconnect device Internal
Mode of protection (L+) - (L-)
(L+) - PE
(L-) - PE
Mounting type DIN rail: 35 mm
Color traffic grey A RAL 7042
Housing material PA 6.6
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, one-piece
Surge protection fault message Optical, remote indicator contact
Back to top
 

Additional descriptions

Note The product is also suitable for applications in PV systems with a max. short-circuit current ISCPV = 15 kA (according to EN 50539-11:2013).
Back to top
 

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV 1500 V DC
Short-circuit current rating ISCPV 2000 A
Continuous operating current ICPV < 55 µA
Rated load current IL 50 A
Residual current IPE ≤ 55 µA DC
≤ 430 µA AC
Standby power consumption PC ≤ 85 mVA
Nominal discharge current (8/20) µs 20 kA
Maximum discharge current Imax (8/20) µs 40 kA
Total discharge current Itotal (8/20) µs 40 kA
Voltage protection level Up ≤ 4.5 kV
Residual voltage Ures ≤ 4.5 kV (at In)
≤ 3.3 kV (at 3 kA)
≤ 3.6 kV (at 6.25 kA)
≤ 3.8 kV (at 10 kA)
≤ 4.2 kV (at 15 kA)
≤ 5.4 kV (at 40 kA)
Response time tA ≤ 25 ns
Insulation resistance Riso > 5 GΩ (at 500 V DC)